The unit is installed in a finished room, or used as a visible floor-standing cabinet. Performance data follow the standard-motor ratings for each size; the LM suffix marks the vertical exposed cabinet. FP-xxLM is the vertical exposed (FPLM) version of size FP-xx. Example: FP-51 and FP-51LM share the same size and performance data. Concealed vertical and larger cabinet units are listed separately.
Outlet options: inclined outlet, top outlet or front outlet can be selected. Drawings in the official pack show the left-hand (left-piping) arrangement. All three outlet options use the same cabinet depth of 240 mm.
Additional catalogue photographs of vertical exposed fan coil units are on the Air conditioning & fan coils page. Open that gallery →
Photographs and drawings
Style photographs come from the official FPLM English pack. Contact watermarks on those photographs are kept. Click to enlarge.
Click to enlargeVertical exposed unit — white cabinet, curved outlet
Click to enlargeVertical exposed unit — white cabinet, linear grille
Click to enlargeVertical exposed unit — wood-grain cabinet
Click to enlargeVertical exposed unit — brown cabinet
Click to enlargeVertical exposed unit — with display
Click to enlargeVertical exposed unit — with display, oblique view
Click to enlargeInclined outlet arrangement
Click to enlargeFront grille, factory photograph
Click to enlargePipe connections, factory photograph
Click to enlargeOutline drawing from the official pack
Click to enlargeSection drawings from the official packDimensions
Dimensions A and B are in mm, as published in the official pack. Cabinet depth is 240 mm.
| Dimension | FP-34LM | FP-51LM | FP-68LM | FP-85LM | FP-102LM | FP-136LM | FP-170LM | FP-204LM | FP-238LM |
|---|---|---|---|---|---|---|---|---|---|
| A (mm) | 815 | 965 | 1065 | 1200 | 1300 | 1620 | 1720 | 1920 | 2120 |
| B (mm) | 435 | 585 | 685 | 820 | 920 | 1240 | 1340 | 1540 | 1740 |
| Cabinet depth (mm) | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 240 |
Performance data — standard motor
Capacities, airflow and sound are the standard-motor values for this size range, copied from the official English pack. The chilled-water pressure drop for FP-136LM is 8.53 kPa, as printed in that table.
| Parameter | FP-34LM | FP-51LM | FP-68LM | FP-85LM | FP-102LM | FP-136LM | FP-170LM | FP-204LM | FP-238LM |
|---|---|---|---|---|---|---|---|---|---|
| Airflow (m³/h) | |||||||||
| High | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
| Medium | 255 | 383 | 510 | 638 | 765 | 1020 | 1275 | 1530 | 1785 |
| Low | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 |
| Cooling capacity (W) | |||||||||
| High — total | 1888 | 2795 | 3709 | 4625 | 5518 | 7246 | 9038 | 10878 | 12618 |
| High — sensible | 1310 | 1926 | 2528 | 3149 | 3722 | 4863 | 6073 | 7242 | 8389 |
| Medium — total | 1661 | 2432 | 3251 | 4030 | 4785 | 6182 | 7739 | 9158 | 10716 |
| Medium — sensible | 1099 | 1603 | 2133 | 2629 | 3148 | 4072 | 5082 | 6002 | 7040 |
| Low — total | 1321 | 1933 | 2568 | 3182 | 3778 | 4900 | 6136 | 7281 | 8472 |
| Low — sensible | 839 | 1231 | 1623 | 2005 | 2379 | 3120 | 3895 | 4609 | 5408 |
| Heating capacity (W) | |||||||||
| High | 3143 | 4556 | 5997 | 7378 | 8707 | 11410 | 14254 | 16789 | 19476 |
| Medium | 2567 | 3732 | 4915 | 6054 | 7154 | 9395 | 11731 | 13845 | 16064 |
| Low | 1879 | 2746 | 3622 | 4471 | 5295 | 6975 | 8713 | 10296 | 11953 |
| Sound pressure level dB(A) | |||||||||
| Low static (12 Pa) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| High static (30 Pa) | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 |
| Ultra-high static (50 Pa) | 41 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | 56 |
| Water flow and pressure drop | |||||||||
| Water flow (L/h) | 325 | 481 | 638 | 796 | 949 | 1246 | 1555 | 1871 | 2170 |
| Chilled-water pressure drop (kPa) | 2.36 | 5.51 | 10.43 | 17.06 | 25.25 | 8.53 | 13.41 | 20.72 | 29.86 |
| Hot-water pressure drop (kPa) | 1.79 | 4.19 | 7.93 | 10.07 | 19.20 | 6.49 | 10.20 | 15.75 | 22.70 |
| Motor and fan | |||||||||
| Motor quantity | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
| Motor input (W) — low static | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 | 228 |
| Motor input (W) — high static | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 |
| Motor input (W) — ultra-high static | 49 | 66 | 84 | 100 | 118 | 174 | 210 | 250 | 300 |
| Fan quantity | 1 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 |
Motor, fan and coil
- Motor: high-precision bearings (no lubrication required), 3-speed capacitor type, Class B insulation. Power supply: 220 V, 1 ph, 50 Hz.
- Fan: double-inlet, multi-blade, low-noise centrifugal fan. Fan quantity is the same for the standard and ultra-high static-pressure units.
- Coil: thin-wall copper tubes with corrugated aluminium fins and a manual air vent. 3 rows, fin pitch 2.33 mm. Inlet, outlet and condensate connections: 3/4".
Notes from the official pack
- Airflow is the nominal airflow of the standard unit under the rated condition.
- Cooling capacity is based on entering air 27 °C DB / 19.5 °C WB, entering water 7 °C, and a water temperature difference of 5 °C.
- Heating capacity is based on entering air 21 °C DB and entering water 60 °C, with the same water flow as for cooling.
- Low / high / ultra-high static pressure = 12 / 30 / 50 Pa external static pressure, measured at the outlet without grille or filter.
- Performance data in the table are subject to change without notice.
Unit prices printed in the official FPLM pack are not shown on this website. Please send an enquiry for a quotation.